Electrical Current Transformer Testing Equipments With Ac220v ± 10% Power Supply

Brand Name : YUYANG

Model Number : CPT-2

Certification : CE

Place of Origin : China

MOQ : 1 Set

Price : Negotiable

Supply Ability : 100 sets per month

Delivery Time : 15 days

Packaging Details : Plywood case

Keyword : CT PT Testing Equipment

Test standard : IEC60044-1, IEC60044-6, IEC60044-2, IEC60044-5, C57.13

Power supply : AC220V±10%, 50/60Hz±10%

Display : LCD touch screen

Memory capacity : >1000 groups

Software : English

Test object : ct and pt

Warranty : 1 Year

Contact Now

CT VT Testing Equipment for Current and Voltage Transformer Test

Testing for current transformer equipment:

1 Excitation curve and parameters test
2 Turns ratio test
3 Ratio and phase error test
4 Polarity mark check
5 Winding resistance measurement
6 Secondary loop burden measurement
7 Error line curve test for protection CT
8 Transient CT parameters test
9 CT nameplate guess
10 Saturation hysteresis loop curve measurement

Testing for Voltage Transformer equipment

1 Turns ratio test
2 Ratio error and phase angle error test
3 Polarity test
4 Secondary burden test
5 Winding resistance test

Applications of CT/ VT Testing Equipment:

1 CT nameplate check
2 CT parameters check in work burden
3 CT transient parameters analysis
4 CT ratio and phase error calibration
5 VT routine test

Specifications:

Item Name CT and VT Testing Equipment
Test standards IEC60044-1, IEC60044-6, IEC60044-2, IEC60044-5, C57.13
Power supply AC220V±10%, 50/60Hz±10%
Voltage output 0.1~180V (AC)
Current output 0.001~5A(RMS)
Power output 500VA
Max. knee voltage measurement 45KV
Current measurement
Range 0~10A (automatically change range in 0.1/0.4/2/10A)
Error <±0.1%+0.01%FS

Voltage measurement Range 0~200V (automatically change range in 1V/10V/70V/200V)
Error < ±0.1%+0.01%FS
Turns ratio measurement Range 1~35000
1~2000, error<0.05%
2000~5000,error<0.1%
5000~35000,error<0.2%
Phase measurement error ±2min
resolution 0.01min
Winding resistance measurement
Range 0~8kΩ (automatically change range in2ohm/20ohm/80ohm/800ohm/8kohm)
Error < 0.2%RDG+0.02%FS
Maximum resolution : 0.1mΩ
Temperature measurement -50~100 Celsius degree; error<3 Celsius degree
CT Secondary burden Range 0~160ohm (automatically change range in 2ohm/20ohm/80ohm/160ohm)
Error <0.2%RDG+0.02%FS
Maximum resolution : 0.001ohm


PT Secondary burden
Error 0~80kohm (automatically change range in 800ohm/8kohm/80kohm)
Maximum <0.2%RDG+0.02%FS
resolution 0.1ohm

PT ratio measurement

Range
1~35000
1~10000 error<0.1%
10000~35000 error<0.2%
PT ratio error measurement :Typical error<0.05%,
Maximum Error<0.1%
PT phase angle measurement maximum error < 3min
Make evaluation for test results according to selected standards
Make word report for test result
Make word reports one time for multi-group test records on the PC
Calculate the ratio errors and phase angle errors at rated burden and working burden in one time test
Compare excitation curves with saved excitation curves in the same window
Memory capacity >1000 groups test results
Working condition temperature -10℃~50℃; moist ≤90%

Electrical Current Transformer Testing Equipments With Ac220v ± 10% Power SupplyElectrical Current Transformer Testing Equipments With Ac220v ± 10% Power Supply


Product Tags:

electrical test equipment

      

electrical test kit

      
China Electrical Current Transformer Testing Equipments With Ac220v ± 10% Power Supply wholesale

Electrical Current Transformer Testing Equipments With Ac220v ± 10% Power Supply Images

Inquiry Cart 0
Send your message to this supplier
 
*From:
*To: DONGGUAN YUYANG INSTRUMENT CO., LTD
*Subject:
*Message:
Characters Remaining: (0/3000)